Sizing Calculation Spreadsheet Vertical Geothermal Borefields

Abstract : A simple design procedure for single and multiple borehole configurations for designing vertical geothermal systems based on the borehole sizing equation given in ASHRAE Handbook is presented. Sizing equation proposed by S.P. Kavanaugh and K. Rafferty and recast by M. Bernier is used that is derived by assuming that heat transfer in the ground occurs only by conduction and that moisture evaporation and underground water movement are not significant. For single borehole, it is found that on an annual basis, the net amount of heat rejected into the ground is equivalent to a heat pump operating one-eighth of the time, which corresponds to 1.5 kW. Iterative method is used for multiple boreholes, and it is found that in this case borefield length is 10 150 m with a corresponding borehole depth of 84.6 m and temperature penalty T p is -0.24°C after 10 years of operation
Liste complète des métadonnées

https://hal-brgm.archives-ouvertes.fr/hal-00564405
Contributeur : Anne-Marie Pouget Connectez-vous pour contacter le contributeur
Soumis le : mardi 8 février 2011 - 18:26:56
Dernière modification le : mardi 28 juin 2022 - 16:56:10

Identifiants

  • HAL Id : hal-00564405, version 1

Citation

Mikael Philippe, Michel Bernier, Dominique Marchio. Sizing Calculation Spreadsheet Vertical Geothermal Borefields. ASHRAE Journal, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2010, 52 (7), pp.20-+. ⟨hal-00564405⟩